SPD
EE
DC Voltage Surge Protective Device
DC
Installation, Operation
& Maintenance Manual
(800) 237-4567
·
(727) 535-6339
·
Fax (727) 539-8955
Advanced Protection Technologies
www.aptsurge.com
·
14550 58th Street North
·
Clearwater, Florida 33760
UL is a registered trademark of Underwriters Laboratories, NEC
®
and National Electrical Code are
registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002,
C62.45-2002, C62.72-2007 are registered trademarks of IEEE.
10.9.12.lh #8379
European Authorized Representative
Obelis s.a.
Boulevard Général Wahis 53
1030 Brussels, BELGIUM
Tel: +(32) 2. 732.59.54
Fax: +(32) 2. 732.60.03
DC Voltage Photovoltaic System Instructions – Do Not Use for AC Voltage Installation
Save These Instructions - This manual contains important instructions that shall be followed
during installation and maintenance of the power system.
Presently, there is no dedicated UL standard
for higher voltage DC SPDs. The following
SPDees comply with most recent regulatory
actions including UL 1449 Third Edition
Listing (VZCA.E321351) and compliance to
the UL Certication Requirement Decision
(CRD) regarding DC rated SPDs for
Photovoltaic Systems. UL 1449 certication
requires AC voltage specific language,
which is also included below.
Thank you for choosing an APT SPDee Surge Protective Device (SPD). SPDee is a high quality, high
energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages.
SPDee is parallel connected such that circuit ampacity is unlimited. Proper installation is important to
maximize performance. Please follow steps outlined herein. These instructions are not intended to replace
national or local codes. Follow all applicable electrical codes to ensure compliance.
UL 1449 Third Edition (Sept 2009), 2008 NEC
®
Article 285 and CSA C22.1 (CEC) generated substantial
changes regarding AC voltage SPDs.
Be aware that photovoltaic systems generate maximum
voltage at coldest temperatures and brightest light. For
example, full sunup after a cool/cold night produces
maximum voltage on photovoltaic systems. The system’s
maximum voltage rating should take this into account.
The following graphic on the SPD’s label represents DC
voltage:
ENGLISH
Read this manual in entirety prior to installing
Only qualied licensed electricians should install or service SPDs
SPDs should never be installed or serviced when energized or during electrical storms
Use appropriate safety precautions including Personal Protection Equipment
Failure to follow these instructions can result in death, serious injury, and/or
equipment damage
When used in outdoor applications, customer must seal the conduit nipple using
watertight ttings (not included) to ensure a watertight connection
WARNING
– Risk of Electric Shock
TABLE 1:
Range of Input
Operating Voltage
Maximum Input
Voltage
S50A300VDC 0 – 375V DC 424V DC
S50A600VDC 0 – 750V DC 905V DC
S50A1000VDC 0 – 1000V DC 1188V DC
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - & Maintenance Manual

SPDEEDC Voltage Surge Protective DeviceDCInstallation, Operation & Maintenance Manual(800) 237-4567·(727) 535-6339 · Fax (727) 539-8955 Advanced P

Page 2 - INSTALLATION

2Leads: Short & Straight: Cut excess; Do not coil or loopX Not GoodGOODCut off Excess Length Do Not Loop or CoilShort & StraightFigure 1 Figur

Page 3 - Sized for std 35mm DIN-rail

replacing the device. SPDee is ultrasonically welded closed and contains no user serviceable parts.Voltage Rating & Application Before installing

Page 4 - ▪ Do Not Hi-Pot Test

NORMAL OPERATIONGreen LED Indicator – The LED indicator illuminates when the SPD is energized and operating correctly. Indicator operation: Every supp

Page 5 - Operación & Mantenimiento

SPDEEDC Voltage Surge Protective DeviceDCManual de Instalación, Operación & Mantenimiento(800) 237-4567·(727) 535-6339 · Fax (727) 539-8955 Advanc

Page 6 - ADVERTENCIA

2Conductor: Corto y Directo: Exceso de conductor; No enrollar o hacer buclesX MALOBUENOCortar el exceso de cableCorto y DirectoFigura 1 Figura 2Juntas

Page 7 - Figura 5

3Rango de Voltaje y AplicaciónAntes de la instalación del DPS, verique que el voltaje en la placa de identicación y el número del modelo tengan el

Page 8

OPERACIÓN NORMALIndicador LED verde - El LED indicador ilumina cuando el DPS está energizado y operando correctamente. Operación del indicador: Cada e